Evaluation of transmission line arresters against winter lightning
Author/Authors :
Wakai، نويسنده , , T.، نويسنده , , Itamoto، نويسنده , , N.، نويسنده , , Sakai، نويسنده , , T.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
The authors have tested 154 kV-class transmission
line arresters by installing them on an instrumented tower of
a double-circuit test transmission line during winter seasons
since 1993. The tower is struck by natural and artificially-triggered
lightning several times during each winter season. The
conventional transmission line arrester designed against summer
lightning was effective against winter lightning. The authors
developed a new transmission line arrester of reduced rating,
and investigated its applicability against winter lightning based
on EMTP analysis, taking account of measured lightning current
waveforms in winter. Although omission of an earth wire is not
feasible on transmission towers having high footing resistance, the
new arrester of reduced rating is a reasonable option to realize a
line of high lightning performance.
Keywords :
Transmission line arrester , winter lightning , EMTP.