Title of article :
Investigation of the use of inverter control strategy instead of synchronous condensers at inverter terminal of an HVDC system
Author/Authors :
Jovcic، نويسنده , , D.، نويسنده , , Pahalawaththa، نويسنده , , N.، نويسنده , , Zavahir، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
This paper presents a comparison of performance of
traditionally used Synchronous Condensers (SC’s) at inverter side
HVDC terminal and a novel inverter control method. The novel
controller has earlier demonstrated good responses with very weak
inverter AC systems and widely changing AC system parameters.
The aim of this research is to study if it is possible to offer adequate
replacement for SC at weak HVDC -HVAC interconnection point.
The simulation results on an actual HVDC system show excellent
small signal responses, but the main obstacle for the application of
the new control method could be increased probability of commutation
failure. Subsequent tests show that in order to keep the same
commutation failure probability, half of the SC must be maintained
in normal operation. Further SC can also be disconnected, when
the new control method is employed, however the nominal operating
angle has to be somewhat increased. The cost benefit study is
performed to analyze the financial benefits of the proposed project.
It is concluded that, although the benefits are evident for the new
HVDC links, the proposed replacement of SC may not be justifiable
for the existing links.
Keywords :
power system dynamicstability. , HVDC transmission control
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY