Title of article :
A new technique for transformer protection based on transient detection
Author/Authors :
Zhiqian Bo، نويسنده , , Weller، نويسنده , , G.، نويسنده , , Lomas، نويسنده , , T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
This paper proposes a new technique for transformer
protection. The technique is concerned with the detection of the
fault generated high frequency current transients by means of a
specially designed relay unit. The relay, tuned to a band of high
frequencies, is used to capture the transient currents from both
sides of the transformer; the differential and average currents between
the two sides are then calculated. The spectral energies of
these current signals are extracted to produce the operate and restraint
signals; a comparison between the levels of the two signals
determines whether the fault is internal or external to the protected
zone. A new technique for inrush detection has also been
proposed in this paper. The technique detects inrush current by
using the high frequency components contained in its current transient
signal. The restraint signal is derived by computing the ratio
of the spectral energy of the transient signal to the fundamental
current. A comparison between the level of restraint signal and a
pre-defined threshold determines whether a magnetizing inrush is
in process. Simulation studies with respect to different fault and
inrush conditions have been conducted, and the results prove that
the proposed technique is able to offer fast responses in protection
and accurately discriminate between inrush magnetizing current
and internal faults.
Keywords :
transient based protection , transformer protection. , Inrush detection
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY