Title of article :
A study of current-carrying capacity of drawlead cable in condenser bushing
Author/Authors :
Daxiong Zeng، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
6
From page :
925
To page :
930
Abstract :
Temperature rise distribution at the drawlead cables in the condenser bushings was studied with a thermal model and actual thermal tests. Temperature rise of the hottest spot at the cables from the model is consistent with that from the tests within a 10% deviation. Factors that influence working current and overload capacity of the cable were studied. Current-carrying capacities of the drawlead cables with index 105 insulation are presented based on thermal basis of rating.
Keywords :
Bushing , Current-carrying capacity , thermal model , Temperature rise , drawleadcable , thermal test.