Title of article
Electrical design parameters of all-dielectric-self-supporting fiber optic cable
Author/Authors
Tuominen، نويسنده , , M.W.، نويسنده , , Olsen، نويسنده , , R.G.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
8
From page
940
To page
947
Abstract
A lumped circuit model for calculating voltages and
currents on all-dielectric self-supporting (ADSS) fiber optic cable
near high voltage transmission lines has been developed. The model
has been used to show that contamination levels, tower attachment
points, relative ADSS and conductor sag and electrical phasing of
the conductors are important parameters and must be considered
in calculations, especially when determining the possibility of dry
band arcs which could lead to cable damage.
Keywords
high electricfield. , Dry band arcing , fiber optic cables
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2000