Title of article :
Decreasing the commutation failure frequency in HVDC transmission systems
Author/Authors :
Hansen، نويسنده , , A.، نويسنده , , Frank Havemann، نويسنده , , H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
In this paper we show how a fairly large proportion
of those commutation failures that are due to single-phased short
circuits to earth can be avoided. In a control circuit based on a digital
signal processor (DSP) it is possible, with instantaneous results,
to switch from a normal control strategy with equidistant firing
pulses to a strategy that takes into consideration the potentially
dangerous voltage changes on the supply lines.
If the supply voltages are monitored continuously, it is possible
to calculate the necessity of advancing the firing pulses to avoid
commutation failures.
In the paper such a calculation technique is described. The monitoring
times may be approximately 50 sec apart corresponding
to a distance of 0.016 radians or about 1 .
Keywords :
Commutation failures , Digital control , HVDCtransmission.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY