Abstract :
Telephone company customers reported audible noise in their telephone service. Through measurements, analysis, and simulations, 540 Hz noise was found to be coupling from power distribution to telephone cables in a shared underground right-of-way. The source of the noise was small single-phase electronic loads dispersed throughout the power distribution system in the area. A passive shunt filter was designed using an existing capacitor bank. Installation of this filter reduced the noise to acceptable levels.
Keywords :
power system modeling , powersystem simulation , power system harmonics , powerfilters , wire communication interference. , power distribution electromagnetic interference , passivefilters , Harmonic analysis , Grounding , Earth