Title of article :
Fault location using the distributed parameter transmission line model
Author/Authors :
Gopalakrishnan، نويسنده , , A.، نويسنده , , Kezunovic، نويسنده , , M.، نويسنده , , McKenna، نويسنده , , S.M.، نويسنده , , Hamai، نويسنده , , D.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
Earlier work at Texas A&M University led to the development
of transmission line fault location algorithms that were
based on synchronized sampling of the voltage and current data
from the two ends of the line. The line models used in the algorithms
were based on lumped parameter models for electrically
short lines, or lossless distributed parameter models for electrically
long lines. In this paper, the lossless line model is modified
to account for the series losses in the line. The line model equations
are then solved in the time domain to accurately locate the fault.
Testing of the modified algorithm is performed on a power system
belonging to the Western Area Power Administration. Extensive
EMTP based simulations are used to generate data that are supplied
as inputs to the fault location algorithm. To make the testing
as realistic as possible, detailed models of instrument transformers
are used in the simulation of the various fault cases.
Keywords :
Electromagnetic transients , synchronized sampling. , modeling , Fault location
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY