Title of article :
Comparison of thyristor-controlled reactors and voltage-source inverters for compensation of flicker caused by arc furnaces
Author/Authors :
Garcia-Cerrada، نويسنده , , A.، نويسنده , , Garcia-Gonzalez، نويسنده , , P.، نويسنده , , Collantes، نويسنده , , R.، نويسنده , , Gomez، نويسنده , , T.، نويسنده , , Anzola، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
The objective of this paper is to compare the performance
of thyristor-controlled reactors (TCR) and shunt-connected
PWM voltage source inverters (PWM-VSI) for compensation of
flicker caused by arc furnaces. First of all, arc-furnace principles
are presented in order to explain the main characteristics of the
problem. Secondly, traditional TCR control are analyzed. An improved
measuring procedure is suggested to enhance TCR performance
showing that it achieves faster compensation than more traditional
methods. Thirdly, PWM-VSI control for flicker compensation
is described in detail using Park’s transformation. The analysis
shows how real and reactive power control can be decoupled.
Continuous-time and discrete-time models are considered. Finally,
a TCR control and a PWM-VSI control are compared by simulation
using data and measurements from a real arc-furnace installation.
The analysis considers three different periods of the production
cycle: a) bore-down, b) fusion, and c) refining. It is clear from
the results obtained that a shunt-connected PWM-VSI is better
than a TCR for flicker compensation. This can be easily justified
noting that the bandwidth of the PWM-VSI control system is far
better than that of the TCR control. However, the control system
for a PWM-VSI inverter is more complicated than that of a TCR.
Besides, the latter uses a better-established technology than the
former.
Keywords :
Arc furnace , flicker mitigation , TCR control , PWM , voltage source inverter control.