Title of article :
Screening for HVDC system core saturation instability
Author/Authors :
Hasegawa، نويسنده , , T.، نويسنده , , Matsushita، نويسنده , , J.، نويسنده , , Oue، نويسنده , , Y.، نويسنده , , Tomiyama، نويسنده , , K.، نويسنده , , Ihara، نويسنده , , S.، نويسنده , , Pratico، نويسنده , , E.R.، نويسنده , , Walling، نويسنده , , R.A.، نويسنده , , Zhu، نويسنده , , W.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
7
From page :
1291
To page :
1297
Abstract :
Core saturation instability is a condition resulting from excess low-order harmonic ac/dc system interactions, amplified by increasing transformer flux offset which, in turn, is driven by the interaction between the harmonics and the converter. A small signal analysis method has been successfully applied to efficiently screen a variety of conditions for core saturation instability. The screening measures have been defined in terms of the dc system driving point impedances.
Keywords :
Core saturation instability , harmonic amplification , harmonic instability , HVDC system interactions , small signalanalysis method.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400114
Link To Document :
بازگشت