Author/Authors :
Izumi، نويسنده , , K.، نويسنده , , Takahashi، نويسنده , , T.، نويسنده , , Homma، نويسنده , , H.، نويسنده , , Kuroyagi، نويسنده , , T.، نويسنده ,
Abstract :
Based on the results of basic studies on the housings
and FRP cores of polymer composite insulators, a line post type
polymer insulation arm for 154 kV with a truss structure formed
by three polymer insulation arm units; i.e., two horizontal units
with an open angle between them and one suspension unit, was
experimentally manufactured. Samples of the polymer insulation
arm were tested to verify the withstand voltage performance under
a polluted conditions, the impulse and power-frequency withstand
voltage performance, and the mechanical performance by a full
scale test against longitudinal loads.