Title of article :
Insulation co-ordination for gas-insulated transmission lines (GIL)
Author/Authors :
Volcker، نويسنده , , O.، نويسنده , , Koch، نويسنده , , H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
In this paper focus is given to the insulation
co-ordination of a closed system with integrated surge arresters.
The calculations of transient overvoltages are made with typical
applications of the integration of GIL in the 400 kV net of overhead
lines. The overvoltages in the system are calculated and discussed
for system lengths of 1 km and 10 km. Recommendations for such
applications for the insulation levels are given.
The GIL design configuration, the lightning overvoltages of
overhead lines, and the overvoltages in the GIL are discussed
under respect of overvoltage protection measures. Together with
the use of surge arresters the insulation levels due to overvoltages
are discussed.
The insulation co-ordination is a very important measure for
system optimization. Calculated values found for the insulation
level of the GIL were proven with type tests and long duration test
set-ups. Some test results are also explained in this paper.
Keywords :
transientovervoltages , N2/SF6-gas mixture , insulationco-ordination , integrated surge arresters , remote stroke , long duration test , nearby direct stroke , Gas-insulated transmission line , type testing.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY