Title of article :
Diagnostics and monitoring of metal-oxide surge arresters in high-voltage networks-comparison of existing and newly developed procedures
Author/Authors :
Heinrich، نويسنده , , C.، نويسنده , , Hinrichsen، نويسنده , , V.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
Various diagnostic methods—either on-line or
off-line—for monitoring of metal-oxide surge arresters in
power systems are known. In most cases they are based on
the measurement of the leakage current. This paper describes
the most important ones in detail, such as measuring of the
– -characteristics or analysis of the third harmonic content of
the leakage current. Their advantages and weak points, respectively,
are discussed, basing on most recent investigation results
on the change of the – -characteristics due to electrical and
nonelectrical stresses.
It turns out that nearly none of these commonly applied methods
really work satisfactory under either technical or economical
aspects. As an alternative the temperature of the MO-insert
is proposed to be used for diagnostics purposes. This is made
possible by newly developed passive temperature sensors, which
can be remotely accessed without any hardware connection to
the environment. It is shown how the temperature can be used
for monitoring of all kinds of degradation, energy absorption,
thermal stability or even pollution performance.
Keywords :
MO-arrester , diagnostics , monitoring , third harmonic. , resistive current , temperature , Power loss , Degradation
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY