Title of article
Influence of fault arc characteristics on the accuracy of digital fault locators
Author/Authors
Funabashi، نويسنده , , T.، نويسنده , , Otoguro، Y. نويسنده , , H.، نويسنده , , Mizuma، نويسنده , , Y.، نويسنده , , Dube، نويسنده , , L.، نويسنده , , Kizilcay، نويسنده , , F.، نويسنده , , Ametani، نويسنده , , A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
5
From page
195
To page
199
Abstract
This paper has proposed a time domain model of a
fault locator with special reference to fault arc nonlinearities by applying
the MODELS language of the EMTP. It has been found that
an impedance relay type locator is significantly influenced by the
fault arc nonlinearities, while the current diversion ratio method is
not influenced. This validates the advantage of the current diversion
approach over the impedance approach.
Keywords
ATP-EMTP , fault arc , fault locator , time domain model. , models