Title of article :
Elimination of transformer inrush currents by controlled switching. II. Application and performance considerations
Author/Authors :
Brunke، نويسنده , , J.H.، نويسنده , , Frohlich، نويسنده , , K.J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
Transformer inrush currents are high-magnitude,
harmonic-rich currents generated when transformer cores are
driven into saturation during energization. These currents have
undesirable effects, including potential damage or loss-of-life
to the transformer, protective relay misoperation, and reduced
power quality on the system. Controlled transformer switching
can potentially eliminate these transients if residual core and core
flux transients are taken into account in the closing algorithm.
This paper explores the practical considerations of core flux
transients, performance of control strategies, and the application
of circuit breakers to control transformer inrush transients.
Keywords :
Controlled switching , inrush current , residualflux , transformer switching.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY