Title of article :
Elimination of transformer inrush currents by controlled switching. II. Application and performance considerations
Author/Authors :
Brunke، نويسنده , , J.H.، نويسنده , , Frohlich، نويسنده , , K.J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
5
From page :
281
To page :
285
Abstract :
Transformer inrush currents are high-magnitude, harmonic-rich currents generated when transformer cores are driven into saturation during energization. These currents have undesirable effects, including potential damage or loss-of-life to the transformer, protective relay misoperation, and reduced power quality on the system. Controlled transformer switching can potentially eliminate these transients if residual core and core flux transients are taken into account in the closing algorithm. This paper explores the practical considerations of core flux transients, performance of control strategies, and the application of circuit breakers to control transformer inrush transients.
Keywords :
Controlled switching , inrush current , residualflux , transformer switching.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2001
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400192
Link To Document :
بازگشت