Title of article
Improved calculations for no-load transformer switching surges
Author/Authors
Popov، نويسنده , , M.، نويسنده , , van der Sluis، نويسنده , , L.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
8
From page
401
To page
408
Abstract
This paper deals with a modeling of components and
calculation of transient overvoltages that build up on the transformer
primary terminals after the transformer has been switched
off by a vacuum circuit breaker (VCB). The transformer is connected
to the circuit breaker by a cable. The transient overvoltages
are calculated for different cable lengths, and the cumulative probability
of different arc angles is investigated.
In this study two cases are considered: transient overvoltages
due to steady-state magnetizing current switching, and transient
overvoltages due to inrush current switching. It is shown that the
case of inrush current switching is worse, as virtual current chopping
is possible. The cable is modeled by pi sections, whereas the
transformer model is based on a terminal impedance. The VCB
re-ignitions are modeled by means of withstand voltage characteristics
and high-frequency quenching capability. Due to shortage of
field tests, this work uses only literature references to compare the
results with actual measurements.