This paper presents an algorithm for CT saturation
detection based on the measurement of the power system source
impedance seen at the relay location. The algorithm estimates
this source impedance using a short-data window impedanceestimation
algorithm and samples taken from the Current Transformer
(CT) secondary current and bus-bar voltage. Following the
changes on the impedance seen at the relay location, the algorithm
is able to detect a CT saturation and send a blocking order to a
fast tripping bus-bar differential relay.