Title of article
A combined directional and faulted phase selector element based on incremental quantities
Author/Authors
Benmouyal، نويسنده , , G.، نويسنده , , Mahseredjian، نويسنده , , J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
7
From page
478
To page
484
Abstract
In this paper differential incremental or superimposed
voltage and current quantities are used in order to
determine directionality of a fault in a network. It is shown that
this can be accomplished by performing three scalar products
between three voltage and current phasor pairs. The relative levels
of these same three scalar products can be furthermore used to
identify the faulted phases. While, in ultra-high-speed directional
comparison relays, superimposed voltage and current had to be
treated in the time domain in order to get speed, in this paper all
computations are done in the frequency domain.
Keywords
Digital Relaying , protectiverelays , directional element , single pole tripping.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2001
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400223
Link To Document