Title of article :
Condition assessment and failure modes of solid dielectric cables in perspective
Author/Authors :
Abdolall، نويسنده , , K. Halldorson، نويسنده , , G.L. Green، نويسنده , , D. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
Older solid dielectric cables are now approaching the
end of their life and failing. Consequently there has been a sustained
effort for the development of techniques to assess the remaining
life of in-service cables for the purpose of establishing replacement
criteria. Because of the generally accepted belief that the
failure mode is due to the aging of the insulation, these techniques
have mainly focused on measuring changes in the electrical properties
of the insulation. However, it has been determined that there
are other failure modes associated with loss of the protective function
of the jacketing material leading to corrosion and breaks in
the metallic shields and poor contact between semicon and metallic
shield, causing arcing damage and eventual failure of the cable.
This failure mode is more prevalent in cables operated in a harsh
chemical environment.
This paper presents the results of a research program aimed at
developing a test protocol that is based on evaluating the condition
of all the cable components and not just the insulation. The tests
were designed to evaluate the condition of jacket, extent of corrosion
of the metallic shield, and degree of degradation of the cable
insulation. The results are discussed in terms of correlations between
the field measurement parameters and the condition of the
cable, and prioritization criteria for cable replacement.
Keywords :
Condition assessment of solid dielectric cables , neutral corrosion. , failure modes of solid dielectric cable
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY