Title of article
A new digital relay for generator protection against asymmetrical faults
Author/Authors
Usta، نويسنده , , O. Bayrak، نويسنده , , M. Redfern، نويسنده , , M.A. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
6
From page
54
To page
59
Abstract
Under unbalanced conditions the three phase instantaneous
power oscillates at twice the power system frequency. The
magnitude of these oscillations can be used as a measure of the
system unbalance. This paper has introduced a new digital relaying
algorithm designed to detect asymmetrical faults by monitoring the
sinusoidal oscillations of the three-phase instantaneous power measured
at the generator terminal. Once an asymmetrical fault is detected,
the algorithm checks the direction of the negative sequencereactive
power flow at the machine terminal to discriminate between
internal and external faults. Power system test studies presented
show that the new relay provides fast tripping for internal
asymmetrical faults and back up protection for external asymmetrical
fault conditions.