Abstract :
Under unbalanced conditions the three phase instantaneous
power oscillates at twice the power system frequency. The
magnitude of these oscillations can be used as a measure of the
system unbalance. This paper has introduced a new digital relaying
algorithm designed to detect asymmetrical faults by monitoring the
sinusoidal oscillations of the three-phase instantaneous power measured
at the generator terminal. Once an asymmetrical fault is detected,
the algorithm checks the direction of the negative sequencereactive
power flow at the machine terminal to discriminate between
internal and external faults. Power system test studies presented
show that the new relay provides fast tripping for internal
asymmetrical faults and back up protection for external asymmetrical
fault conditions.