Title of article :
An adaptive scheme for parallel-line distance protection
Author/Authors :
Yi Hu Novosel، نويسنده , , D. Saha، نويسنده , , M.M. Leitloff، نويسنده , , V. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper describes an adaptive protective relaying
scheme for parallel-line distance protection. The scheme adjusts its
operation based on the availability of input signals to achieve an optimal
distance protection performance on parallel lines influenced
by mutual coupling effect. When available, zero sequence current
from the parallel line is used to fully compensate the mutual coupling
effect. The zero sequence current ratio is used to avoid possible
false operations on healthy lines, which may result from such
compensation. When the parallel line’s zero sequence current is
not available, the line operating status is used instead to select the
proper zero sequence current compensation factors in impedance
calculation. Default zero sequence current compensation factor is
used when both the parallel line’s zero sequence current and line
operating status signals are not available. The performance of the
scheme has been verified on a simulated network and the results
are presented.
Keywords :
adaptive systems , coupled transmission lines , distancemeasurement , mutual coupling , protective relaying.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :