Title of article :
A new adaptive PMU based protection scheme for transposed/untransposed parallel transmission lines
Author/Authors :
Ching-Shan Chen، نويسنده , , Chih-Wen Liu، نويسنده , , Joe-Air Jiang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
10
From page :
395
To page :
404
Abstract :
This paper proposes a brand-new adaptive phasor measurement unit (PMU) based protection scheme for both transposed and untransposed parallel transmission lines. The development of the scheme is based on the distributed line model and the synchronized phasor measurements at both ends of lines. By means of eigenvalue/eigenvector theory to decouple the mutual coupling effects between parallel lines, the fault detection and location indices are derived. The two proposed indices are used in coordination such that the internal and external fault events can be distinguished completely. By on-line estimating the line parameters under the actual power system conditions, the proposed scheme will respond more accurately to power system faults. Extensive simulation results using EMTP have verified that the accuracy of the fault location achieved is up to 99.9%. The proposed protection system responds well and fast with regard to dependability and security. All the results show that the performance of the proposed detection/location indices is independent of fault types, locations, resistance, source impedance, fault inception angles, and load flows.
Keywords :
Digital protection , computer relaying , fault detection/location , Parallel transmission lines , phasor measurement unit(PMU).
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400348
Link To Document :
بازگشت