Title of article :
Fault location using voltage measurements
Author/Authors :
Galijasevic، Semira نويسنده , , Z.، نويسنده , , Abur، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
5
From page :
441
To page :
445
Abstract :
This paper presents a novel method for locating short-circuit faults in electric power systems. The origins of the method are in the concept of vulnerability contours which is used in assessing the likelihood of voltage sags effecting a given network area. The method is applied in an off-line step and an on-line step. On-line step consists of measuring voltage sags at selected system buses. Off-line step consists of estimating the most likely fault location by matching measured voltage sags with the ones calculated through the fault simulations. In the process, the fault resistance is estimated as well. To cope with the inherent uncertainty in the problem, the fuzzy logic reasoning is applied. The performance of the method is demonstrated using some typical examples. Since the actual measurements of voltage sags were unavailable, fault simulations were conducted to emulate real measuring process.
Keywords :
Fault location , fault simulation , fuzzy logic.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400355
Link To Document :
بازگشت