Title of article :
Wavelet-based data compression of power system disturbances using the minimum description length criterion
Author/Authors :
Hamid، نويسنده , , E.Y.، نويسنده , , Kawasaki، نويسنده , , Z.-I.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper introduces a compression technique for
power disturbance data via discrete wavelet transform (DWT)
and wavelet packet transform (WPT). The data compression leads
to a potential application for remote power protection and power
quality monitoring. The compression technique is performed
through signal decomposition up to a certain level, thresholding
of wavelet coefficients, and signal reconstruction. The choice of
which wavelet to use for the compression is of critical importance,
because the wavelet affects reconstructed signal quality and the
design of the system as a whole. The minimum description length
(MDL) criterion is proposed for the selection of an appropriate
wavelet filter. This criterion permits to select not only the suitable
wavelet filter but also the best number of wavelet retained
coefficients for signal reconstruction. The experimental study has
been carried out for a single-phase to ground fault event, and the
data compression results of using the suitable wavelet filter show
that the compression ratios are less than 11% and are reduced
to more than a half of that percentage value by implementing an
additional lossless coding.