Title of article :
Transient recovery voltages requirements for system source fault interrupting by small generator circuit breakers
Author/Authors :
Dufournet، نويسنده , , D.، نويسنده , , Montillet، نويسنده , , G.F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
5
From page :
474
To page :
478
Abstract :
Recent years have seen an increasing development of small generations of electric power. These generators of relatively low power, equal or less than 100 MVA, are protected in an economic way by generator circuit breakers which are located between the generator and the step-up transformer. In 1997 the IEEE Switchgear Committee has issued a new edition of its standard C37-013 for generator circuit breakers, which covers mainly the applications with power transformers rated 100 MVA and above [1]. A revision of this standard is currently prepared by the IEEE Switchgear Committee in order to broaden its scope to all generator circuit breakers. The purpose of this paper is to contribute to the definition of TRV requirements for system-source faults in the case of small generator circuit breakers connected to the step-up transformer by cables.
Keywords :
generator circuitbreakers. , AC high voltage generator
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400360