• Title of article

    How to avoid unstable time domain responses caused by transformer models

  • Author/Authors

    Henriksen، نويسنده , , T.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    7
  • From page
    516
  • To page
    522
  • Abstract
    Modeling a three-winding transformer gives occasionally a negative reactance that may result in an unstable circuit. This unstable condition can be eliminated by neglecting the magnetizing losses or taking them into account in a different way as shown in this paper. Unstable responses are, under certain conditions, extremely dependent on the time step when using EMTP or similar programs. This paper shows why simulated terminal voltages do not always reveal an unstable circuit condition.
  • Keywords
    negative inductance , Transformers , time domain analysis , unstable circuit. , MODELING
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2002
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number