Title of article :
Unbalance protection of fuseless, split-wye, grounded, shunt capacitor banks
Author/Authors :
Horton، نويسنده , , R.، نويسنده , , Warren، نويسنده , , T.، نويسنده , , Fender، نويسنده , , K.، نويسنده , , Harry، نويسنده , , S.، نويسنده , , Gross، نويسنده , , C.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
4
From page :
698
To page :
701
Abstract :
In recent years, a large number of electric utilities have been implementing fuseless split-wye grounded capacitor banks in lieu of the traditional externally fused bank. This change in philosophy has forced many protection engineers to research new methods of calculating the quantities needed to apply unbalance protection. This paper presents a novel method of calculating the unbalance current produced by fuseless capacitor unit failures as well as some general background information regarding fuseless split-wye grounded capacitor bank technology and unbalanced protection.
Keywords :
Power capacitors , power system protection.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400392
Link To Document :
بازگشت