Title of article
A novel adaptive PMU-based transmission-line relay-design and EMTP simulation results
Author/Authors
Jiang، نويسنده , , J.-A.، نويسنده , , Chih-Wen Liu، نويسنده , , Ching-Shan Chen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
8
From page
930
To page
937
Abstract
This paper proposes a novel adaptive relaying
scheme based on phasor-measurement units (PMUs) for transmission
lines. The proposed adaptive relaying scheme can provide
an extremely accurate discrimination between in-zone and
out-of-zone faults. Two novel and composite fault discrimination
indices in terms of Clarke components of synchronized voltage
and current phasors at two ends of a line are derived. A line
parameter estimation algorithm is developed and built in the
newly designed relay to solve the uncertainty problem of line
parameters. The proposed relaying scheme is independent of fault
types, fault locations, fault path resistance, fault inception angles,
and the variations of source impedance. The tripping decision
time of the designed relay is very fast and almost held well within
6 ms for most fault events. All of the EMTP simulation results
show that the proposed adaptive relaying scheme provides a high
level of dependability and security.