Title of article :
Proposed standards for frequency conversion factors of transformer performance parameters
Author/Authors :
Girgis، نويسنده , , R.S.، نويسنده , , teNyenhuis، نويسنده , , E.G.، نويسنده , , Beaster، نويسنده , , B.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
6
From page :
1262
To page :
1267
Abstract :
This paper presents the development of appropriate frequency conversion factors for performance parameters of transformers. These factors are needed in order to allow manufacturers to convert measured values from 60 to 50 Hz and vice versa. Conversion factors are necessary when equipment at a manufacturer’s test facility allows direct measurement at one frequency and not the other. These factors are developed in this paper for no load loss, exciting current, load loss, and noise level using both analytical and actual tested data. Measured data, provided by several manufacturers, were used to confirm the theoretical results. This paper will be used as a basis for proposing standard frequency conversion factors in the IEEE/ANSI [1] and IEC test standards for power and distribution transformers. Such a standard will make it possible for manufacturers to use the same frequency conversion factors, and hence, have a more uniform accuracy of the reported test data at both 50 and 60 Hz.
Keywords :
Frequency conversion , test standards , transformers.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2003
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400500
Link To Document :
بازگشت