Abstract :
The independent control of active and reactive power
flow in a transmission line is necessary for the transfer of bulk
power along a desired path in the most economical way. A “Sen”
Transformer (ST) uses transformer and tap changers that are
traditionally used to build a voltage-regulating transformer (VRT)
and a phase angle regulator (PAR). The ST regulates the voltage
at a point in the transmission line as a VRT does. Additionally,
the ST provides an independent and bidirectional active and
reactive power ( and ) flow control in the transmission line
as a voltage-sourced converter (VSC)-based unified power flow
controller (UPFC) does. Although both the ST and the PAR use
a comparable number of components, the ST provides an area
of controllability in the - plane similar to a UPFC, while
the PAR provides a linear - characteristic. The technology
of transformer and tap changer is proven to be reliable and
cost-effective when compared with the emerging technology of
VSC. The new ST is adequate to provide independent control of
active and reactive power flow in most utility applications.