Title of article :
A CT Saturation Detection Algorithm
Author/Authors :
Y.-C. Kang، نويسنده , , S.-H. Ok، نويسنده , , and S.-H. Kang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
This paper proposes an algorithm for detecting current
transformer (CT) saturation by analyzing a secondary current.
The current has points of inflection where saturation begins
and ends. Then, discontinuity in the first difference of the current
arises at the next instants of points of inflection, where the
second and third differences of the current may have large values
enough to detect saturation. In this paper, the third difference is
used because it is more effective than the second difference in terms
of saturation detection. However, an anti-aliasing low-pass filter
softens the current and, thus, reduces the values of the third difference
at those instants. This paper includes the effect of a low-pass
filter on the proposed algorithm. The sampling rate of 64 samples/
cycle (s/c) is studied by varying a remanent flux and the cutoff
frequency of the filter. The test results clearly indicate that the
proposed algorithm successfully detects the interval of saturation
even with a remanent flux and the softening effect. However, special
attention should be paid to the decision of the threshold value
when a cutoff frequency is much lower than half the sampling frequency.
This paper concludes by implementing the algorithm into
a TMS320C6701 digital signal processor and the results are satisfactory.
Keywords :
Difference , Low-pass filter , remanent flux. , pointsof inflection , CT saturation
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY