Title of article :
Effects of Hot on Post-Arc Circuit Breaker Design
Author/Authors :
T. Uchii، نويسنده , , S. Nishiwaki، نويسنده , , and S. Boggs، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
SF6 is blown through the arc during interruption of
an SF6 puffer circuit breaker. This hot gas flows down an exhaust
tube into the chamber of a dead tank circuit breaker where it can
lower the dielectric withstand between the exhaust tube and the
tank of the circuit breaker, leading to dielectric breakdown during
the transient recovery voltage after clearing. This paper presents
experimental evidence that any such breakdown is controlled by
the hot gas near the exhaust tube, with cold gas in the remainder
of gap having little effect on the breakdown voltage. This experimental
conclusion is supported by a detailed theory for conditions
under which breakdown can occur.
Keywords :
transient recoveryvoltage. , gas circuit breaker , SF6 , ARC
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY