Coolant Flow Distribution and Pressure Loss in ONAN Transformer Windings—Part II: Optimization of Design Parameters
Author/Authors
J. Zhang and X. Li، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
6
From page
194
To page
199
Abstract
The effects of total mass flow rate, flow arrangement,
and geometrical parameters in ONAN transformer windings are
investigated. It is found that the conventional minor losses are predominant
in determining the mass flow distribution and pressure
losses for the present flows. The sizes of the cooling ducts and the
number of disks per pass have strong influence on both the mass
flow distribution and the pressure loss. Flow arrangement in the
horizontal ducts can have significant influence on the flow distribution,
hence on the hot spot formation. Since the rate of heat generation
increases in the vertical direction, a corresponding increase
in the cooling oil flow rate vertically will optimize winding performance.
Keywords
Pressure loss , transformer. , Disk-type , flow distribution , Hydraulic model
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY