Title of article
Mitigation of Lightning-Induced Overvoltages in Medium Voltage Distribution Lines by Means of Periodical Grounding of Shielding Wires and of Surge Arresters: Modeling and Experimental Validation
Author/Authors
and M. Paolone، نويسنده , , C. A. Nucci، نويسنده , , E. Petrache، نويسنده , , and F. Rachidi، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
9
From page
423
To page
431
Abstract
In this paper, we investigate the effect of periodically-
grounded shielding wires and surge arresters on the
attenuation of lightning-induced voltages. We discuss the adequacy
of the commonly made simplification of assuming the
shielding wire at ground potential, instead of being treated as one
of the conductors of the multiconductor system. We also compare
then the mitigation effect of shielding wires with that achievable
by the insertion of surge arresters along the line. The computation
results are first validated by means of calculations obtained by
other authors referring to a simple line configuration, and then by
means of experimental results obtained using a reduced-scale line
model illuminated by a nuclear electromagnetic pulse (NEMP)
simulator. One of the main conclusions is that the effectiveness of
shielding wires and surge arresters depends mostly on the spacing
between two adjacent grounding points or surge arresters.
Keywords
Grounding , lightning-induced voltages , shieldingwire , surge arrester.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400609
Link To Document