Abstract :
This paper presents an investigation about false
operation of vector surge relays due to adjacent feeder faults.
The objective was to explore the scenarios that led to a higher
risk of false operation. Simulation results have shown that the
main factors affecting false operation are system and generator
loading, generator inertia constant, amount of power exported
by the generator, short-circuit level, feeder X R ratio, fault
clearance time, and electrical distance between the generator
and the fault.
Keywords :
Distributed generation , false operation , islandingdetection , Synchronous generators , vector surge relays.