Title of article :
Impact of Difference of Feeder Impedances on the Performance of a Static Transfer Switch
Author/Authors :
H. Mokhtari and M. R. Iravani، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
7
From page :
679
To page :
685
Abstract :
Conventionally, control system of a static transfer switch (STS) is designed based on the assumption that the STS terminal voltages are in-phase. This paper investigates the impact of phase difference of the STS terminal voltages on the STS transfer time and cross current. The phase difference is assumed to be a result of the difference of the feeder impedances. The paper shows that phase differences of even up to 4.5 , which are accompanied by up to 5% voltage drop at the STS terminal, can noticeably increase the transfer time and the cross current magnitude. The studies are conducted on the IEEE STS-l benchmark system using the PSCAD/EMTDC software.
Keywords :
Load transfer , sensitive loads , static transfer switch. , power quality
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400646
Link To Document :
بازگشت