Many network operators are doing important efforts
to collect relevant and precise information about voltage dips in
HV networks. This information is however not relevant for the end
user, who is connected at a lower voltage level, often behind a Dy
transformer and who will not experience the same voltage dips as
recorded by the power quality monitors.
In most cases the power quality monitors only records rms voltages
during dips and the deduction of the characteristics at lower
voltage levels is not possible. The voltage phasors are required to
derive this kind of information.
In this paper a new method is proposed which enables to obtain
valuable statistical information for the network users from existing
monitors and databases, which only contain information about rms
voltages. Algorithms are proposed to estimate the dip type from the
relation between the three rms voltages during the dip. Knowing
the dip type the phasors can be calculated.
Good results are obtained for faults in transmission networks,
especially on overhead lines. The more severe the voltage dip, the
better the performance of the algorithm.