Title of article :
Effects of Symmetrical Voltage Sags on Three-Phase Three-Legged Transformers
Author/Authors :
L. Guasch، نويسنده , , F. C?rcoles، نويسنده , , J. Pedra، نويسنده , , L. Sainz، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
9
From page :
875
To page :
883
Abstract :
This paper describes the effects of symmetrical voltage sags on three-phase three-legged transformers. The transformer model includes saturation and is based on experimental parameters. It has been implemented in PSpice. Voltage recovery after a voltage sag can produce transformer saturation. This saturation produces an inrush current similar to that of the transformer energizing. The variables that influence the peak value of the inrush current, namely depth, duration, and initial point-on-wave are studied. A result that must be emphasized is the periodical influence of the sag duration.
Keywords :
transformer model , Inrush current , voltage sags.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400672
Link To Document :
بازگشت