Title of article :
Radiometric Measurement of Circuit Breaker Interpole Switching Times
Author/Authors :
P. J. Moore، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
Monitoring the switching times of circuit breakers
is important in the condition assessment of the operating mechanism.
Although methods exist for this, they are not applicable
to existing plant without retrofitting. Recent research shows that
arcing produces impulsive radio-frequency radiation. Using direct
digital sampling of the antenna signals, impulses from operating
circuit breakers (CBs) may be recorded. From timing analysis of
the received impulses, the interpole switching time of the CB can
be measured. Results of this method are shown for a field trial on a
132-kV SF6 CB attached to a capacitor bank. The relationship between
the opening and closing impulses is discussed. This method
of timing measurement can be applied to an energized CB. Measurement
of the interpole switching times is completely noninvasive,
whereas the overall switching time requires a clamp CT fitted
on the CB wiring.
Keywords :
Condition monitoring , Impulsive noise , switching times. , radiometric monitoring , highvoltagecircuit breakers , digital monitoring
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY