Title of article :
Real-Time PD Identification in Diagnosis of GIS Using Symmetric and Asymmetric UHF Sensors
Author/Authors :
T. Hoshino، نويسنده , , K. Nojima، نويسنده , , and M. Hanai، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
6
From page :
1072
To page :
1077
Abstract :
A new practical method for real-time insulation diagnosis of gas-insulated switchgear (GIS) has been developed and introduced. A notable technique, which takes the output ratio of a symmetric ultra-high-frequency (UHF) sensor (e.g., a loop electrode) to an asymmetric one (e.g., a conical coupler), makes it possible to immediately identify defects and also to eliminate noises because the output ratio of those UHF sensors strongly depends on the radial position of the GIS. It would be remarkably effective for dc power transmission, intermittent partial discharge (PD), and sequential risk assessment based on each identified PD pulse, which would support condition-based maintenance.
Keywords :
Gas-insulated switchgear (GIS) , insulation diagnosis , Partial discharge (PD) , real-time identification , ultra-highfrequency(UHF) sensor.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400703