Title of article :
High-Frequency Reignition Current and Its Influence on Electrical Durability of Circuit Breakers Associated With
Shunt-Reactor Current Switching
Author/Authors :
H. Tanae، نويسنده , , E. Matsuzaka، نويسنده , , I. Nishida، نويسنده , , I. Matori، نويسنده , , M. Tsukushi، نويسنده , , and K. Hirasawa، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
Very-high-frequency and high-peak reignition currents
were measured in shunt reactor banks rated at 33 kV 40MVA
during breaking operations of a gas circuit breaker (CB). To measure
those kinds of high-frequency transients in reactor circuits in
service, a noninvasive method of measuring was proposed using
Rogowski coils and capacitive coupled antennas. Some combinations
of metals in an electrical collector used in CBs tend to get severely
eroded by the high-frequency reignition currents. The paper
also proposes a test circuit that can yield high-frequency reignition
currents to evaluate the electrical durability of CBs.
Keywords :
Circuit breaker , Current collector , electrical durability , reignition , shunt reactor.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY