Title of article :
Improved Insert Geometry for Reducing Tank-Wall Losses in Pad-Mounted Transformers
Author/Authors :
J. C. Olivares، نويسنده , , R. Escarela-Perez، نويسنده , , S. V. Kulkarni، نويسنده , , F. de Le?n، نويسنده , , E. Melgoza-Vasquez، نويسنده , , and O. Hern?ndez-Anaya، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
7
From page :
1120
To page :
1126
Abstract :
This paper presents a numerical analysis of losses generated in the tank-wall surrounding the high-current bushings of pad-mounted transformers using a three-dimensional (3-D) finite- element approach. Two cases are analyzed to study the impact of inserting small plates of different geometry (located near the high-current phases) on the reduction of tank losses. Significant reductions in stray losses occurring in the tank wall are obtained with plate inserts of low-cost.With the “T” configuration proposed in this paper, we reduce the tank-wall losses by a factor of 1/21 at rated current when compared with the case of tank wall without the stainless-steel plate. A 3-D time-harmonic finite-element model is used to determine the losses in the tank wall. Two load loss tests were carried out on experimental transformers to validate the simulations and effectiveness of the low-cost inserts.
Keywords :
pad-mounted transformer , stainless-steel plate , stray losses , tank-wall losses. , finite-element method , low-voltage conductor
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400710
Link To Document :
بازگشت