Abstract :
This paper introduces an improved power system
impedance measurement technique. The technique injects a short
duration current spike into the supply, and derives the impedance
from the measured current and voltage. The method is shown
to work extremely well under most conditions, by experimental
evaluation using a 45-kVA laboratory prototype. Degradation
is observed when a voltage-source-type power-electronic load is
connected directly to the measurement equipment. An alternative
signal processing strategy, based upon the Prony method is
proposed to improve the estimation under these conditions. This
method also reduces the overall transient data capture time, thus
allowing a faster, online calculation of the impedance.