Title of article :
Transmission System Parameters Optimization— Sensitivity Analysis of Secondary Arc Current and Recovery Voltage
Author/Authors :
M. C. Tavares and C. M. Portela، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
8
From page :
1464
To page :
1471
Abstract :
This paper shows the importance of optimizing the transmission system parameters from its conception, considering the relevant options and possibilities, in order to have a better costperformance result. The presented results were obtained in the study of a real transmission system expansion, based on a 865-km long line. The single-phase auto-reclosing (SPAR) procedure was one of the aspects carefully studied, in order to assure adequate transmission reliability. The secondary arc current was mitigated through the traditional solution of using the neutral reactor on the existing shunt reactor banks, which permitted the reduction of the secondary arc current to acceptable values, assuring natural arc extinction and successful SPAR. The method of obtaining the optimized value for the neutral reactor and its implications on the system performance are important aspects, and are discussed in this paper.
Keywords :
secondaryarc current , transmission system. , Transient analysis , EMTP , optimization , recovery voltage , single-phase auto-reclosing (SPAR)
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400755
Link To Document :
بازگشت