• Title of article

    Grounding resistance measurement analysis of grounding system in vertical-layered soil

  • Author/Authors

    Rong Zeng، نويسنده , , Jinliang He ، نويسنده , , Yanqing Gao ، نويسنده , , Hongyu Liu and Jun Zou ، نويسنده , , Zhicheng Guan ، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    7
  • From page
    1553
  • To page
    1559
  • Abstract
    How to precisely measure the grounding resistance of substations is the fundamental factor to guarantee the safe operation of power systems. The placement rules of test electrodes for the grounding resistance measurement of grounding system in vertical-layered soil were analyzed by the numerical method in this paper. The actual demanded location of the test potential electrode respective to the true grounding resistance of grounding system in different measuring directions changed (in a wide range) when the grounding system was arranged in different soil models. The test error of 0.618 method to measure grounding resistance sometimes is very high. The test route that the test circuit is in parallel with the vertical boundary is recommended for measuring the grounding resistance of grounding system in the vertical-layered soil area. The scientific and suitable measuring method of grounding resistance is based on analyzing the actual soil model and the grounding system structure to obtain the suitable test route and choose the correct compensated point location of the potential electrode.
  • Keywords
    Grounding System , Substation , vertical-layered soil. , Fall of potential method , grounding resistance
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2004
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400766