Title of article :
Melting and breaking characteristics of OPGW strands by lightning
Author/Authors :
Goda، نويسنده , , Y.  Yokoyama، نويسنده , , S.  Watanabe، نويسنده , , S.  Kawano، نويسنده , , T.  Kanda، نويسنده , , S. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
6
From page :
1734
To page :
1739
Abstract :
Some strands were melted and broken in a 140 mm2 OPGW (composite fiber-optic ground wire) in a 187 kV transmission line. It was assumed that this was caused by a lightning strike. DC arc tests simulating lightning strikes were carried out, and the melting and breaking characteristics of OPGW strands were obtained. The electric charge of the lightning strike that damaged the OPGW was estimated from the number of strands broken by the DCarc. In this paper, theDCarc test results, and the test conditions required to simulate a powerful lightning strike are described.
Keywords :
transmission lines. , Arc discharges , Lightning , optical fiber cables