Title of article :
Melting and breaking characteristics of OPGW strands by lightning
Author/Authors :
Goda، نويسنده , , Y. Yokoyama، نويسنده , , S. Watanabe، نويسنده , , S. Kawano، نويسنده , , T. Kanda، نويسنده , , S. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
Some strands were melted and broken in a 140 mm2
OPGW (composite fiber-optic ground wire) in a 187 kV transmission
line. It was assumed that this was caused by a lightning strike.
DC arc tests simulating lightning strikes were carried out, and the
melting and breaking characteristics of OPGW strands were obtained.
The electric charge of the lightning strike that damaged the
OPGW was estimated from the number of strands broken by the
DCarc. In this paper, theDCarc test results, and the test conditions
required to simulate a powerful lightning strike are described.
Keywords :
transmission lines. , Arc discharges , Lightning , optical fiber cables
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY