Title of article :
A 25-MW soft-switching HVDC tap for ±500-kV transmission lines
Author/Authors :
Aredes، نويسنده , , M. Portela، نويسنده , , C. Machado، نويسنده , , F.C. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
This paper presents an optimization of a previously
proposed high-voltage dc current transmission system (HVDC)
tap system where the power rating of the soft-switching dc–dc converter
has been increased to supply medium loads (up to 25 MW)
from 500-kV HVDC transmission lines. This dc–dc converter is
connected in series with a pole of the HVDC transmission line. It
drains energy to a dc capacitor through an air-core transformer
and a single-phase diode rectifier connected at the secondary. A
pulsewidth-modulation (PWM) voltage-source converter is directly
connected to this dc capacitor to supply ac loads. The HVDC
tap comprises all those components and can supply high-quality
power to isolated or interconnected load areas. The controller of
the HVDC tap is independent from the control systems of the main
HVDC converter stations. It does not need any communication
channel to the control of the main HVDC converter stations. A
complete bipolar 500-kV HVDC system, together with a refined
model of dc transmission line were implemented to simulate the
performance of the proposed HVDC tap. It has reveled to be very
robust and to be an attractive solution for feeding small loads
from long dc transmission lines.
Keywords :
HVDC tapping , softswitchingtechniques. , DC–AC power conversion
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY