Title of article :
An Integro-Differential Equation Technique for the Computation of Radiated EMI Due to Corona on HV Power
Transmission Lines
Author/Authors :
S. K. Nayak and M. J. Thomas، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
This paper presents a novel technique for the computation
of radiated electromagnetic interference (EMI) levels due
to corona on high-voltage (HV) transmission lines. The EMI levels
computed using the present technique for variousHVtransmission
lines from around the world matches well with the experimentally
measured values, thus validating the present technique. Using the
technique developed, the influence of transmission line length, distance
of observation point from the line, conductor diameter as well
as the transmission line configuration on the radiated EM field has
been studied. It is seen that for observation points which are close
to the transmission line corridor, the total radiated electric field
remains almost constant for line lengths above 1500 m. For observation
points which are far away, a longer length of the line needs
to be considered for computation of the total electric field. In the
study, it is seen that the transmission line conductor height and line
configuration have marginal influence on the radiated electric field.
Keywords :
radio interference (RI) , corona , radionoise (RN). , electromagnetic interference (EMI) , high-voltage transmission lines
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY