Title of article :
Research on Insulation Design of 22.9-kV High- Superconducting Cable in Korea
Author/Authors :
Y.-S. Kim، نويسنده , , D.-S. Kwag، نويسنده , , H.-J. Kim، نويسنده , , J.-W. Cho، نويسنده , , K.-C. Seong، نويسنده , , and S.-H. Kim، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
The electrical insulation design is important for
high-Tc superconducting (HTS) cable because the cable is operated
in a medium voltage environment. For the insulation
design of HTS cable, it is necessary to investigate the ac, impulse
breakdown, and partial discharge inception stress of a liquid
nitrogen/polypropylene laminated paper composite insulation
system. These results were used to design the electrical insulation
of 22.9-kV-class HTS cable in Korea and cable was manufactured.
A manufactured mini-model HTS cable was evaluated for ac
withstand voltage, impulse withstand voltage, breakdown and
dielectric tangent loss (tan ). From these tests, the cable has
satisfied the standard technical specification of KEPCO in Korea.
The breakdown voltage was 110 kV.
Keywords :
AC withstand voltage , dielectric tangent loss , high-Tc superconducting (HTS) cable , partial discharge inceptionstress.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY