Title of article :
Reliable Busbar Protection With Advanced Zone Selection
Author/Authors :
A. Guzm?n، نويسنده , , B.-L. Qin، نويسنده , , and C. Labuschagne، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
Modern digital relays use innovative algorithms to
fulfill busbar protection requirements of fast operating times
for all busbar faults, security for external faults with heavy
current-transformer (CT) saturation, and minimum delay for
evolving faults. This paper describes a reliable protection system
that includes busbar protection and advanced zone selection; the
protection system is suitable for the protection of multiple busbar
arrangements. The protection system consists of several protection
principles and measuring techniques using instantaneous
and phasor quantities in a unique combination to achieve reliable
busbar protection with minimum CT performance requirements.
Keywords :
Busbar , current-transformer (CT) saturation , differential , Directional , Fault detection , zone selection.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :